UNSYMMETRICAL FAULT CURRENTThis page will demonstrate calculations of two unbalanced fault currents , ie line-to-ground and line-to-line faults. Line-to-ground fault is influenced by positive equence impedance Z1, negative sequence impedance Z2 and zero sequence impedance Z0 while that of Line-to-line fault only involves Z1 and Z2. For this example problem, Z1 is the impedance as calculated in previous page on symmetrical fault. All impedance values are in % on chosen 100,000kVA base. For static plants (eg cable, transformer, source network), Z2 = Z1. In the case of rotating equipment (eg generator), Z2 = 0.73 Z1. Z0 exists only at the point of fault.
I, Current due to 100,000kVA base at fault point (ie 415V) = 100,000 kVA/(1.732 x 0.415 V) = 139,120.5 A If (line to earth) = 3 I x 100/ (Z1 + Z2 + Z3) = 3 x 139,120.5 A x 100/ 2203 % = 18.9 kA If (line to line) = Root (3) x I x 100/ (Z1 + Z2) = Root (3) x 139,120.5 A x 100/ 1368.5 % = 17.6 kA If (symmetrical) = I x 100/ Z1 = 139,120.5 A x 100/ 684.4 % = 20.3 kA (exactly similar to that calculated in symmetrical fault calculation's page)
![]() (1) Distribution of currents throughout the complete network (case: Line-to-ground fault). LINE CURRENTS IN SECONDARY OF TRANSFORMER Line-to-ground fault on Line R, IR = 18,900 A Sequence fault current of line R:
Positive sequence current, I1 = 1/3 ( 18,900) = 6300A Fault currents on Line R IR = I1 + I2 + I0 = 18,900 A (proved !)
Fault currents on Line Y
Fault currents on Line B
LINE CURRENTS IN PRIMARY OF TRANSFORMER turns per phase ratio brought about by delta/star transformation = 240 V/(1.732 x 11000 V)= 0.0126 Irr = IY - IB = -0.0126 (Iy - Ib) = - 0.0126(0 - 0) =0 A Iyy = IB - IR = - 0.0126 (Ib - Ir) = - 0.0126 (0 - 18,900 A) = 238 A Ibb =IR - IY = - 0.0126 (Ir - Iy) = - 0.0126 (18,900 A - 0) = - 238 A negative sign before turn per phase ratio means reversal of line current brought about by cascade delta/star transformation
(2) Distribution of currents throughout the complete network (case: Line-to-line fault). LINE CURRENTS IN SECONDARY OF TRANSFORMER Line-to-line fault on Line R, IR = 17,600 A Sequence fault current of line R: Positive sequence current, I1 = 1/3 (IR + IY /_120° + IB /_240°) = 1/3 (17,600 - 17,600 /_120° + 0 ) = 8800 - j15242 Negative sequence current, I2 = 1/3 (IR + IY /_240° + IB /_120°) = 1/3 (17,600 - 17,600 /_240° + 0 ) = 8800 + j5080.7
Note that line-line fault is influenced by positive and negative sequence only. Fault currents on Line R IR = 17,600 A
Fault currents on Line Y
Fault currents on Line B
LINE CURRENTS IN PRIMARY OF TRANSFORMER turns per phase ratio brought about by delta/star transformation = 240 V/(1.732 x 11000 V)= 0.0126 Irr = IY - IB = -0.0126 (Iy - Ib) = - 0.0126(-17,600 A - 0) = 221.8 A Iyy = IB - IR = - 0.0126 (Ib - Ir) = - 0.0126 (0 - 17,600 A) = 221.8 A Ibb =IR - IY = - 0.0126 (Ir - Iy) = - 0.0126 (17,600 A- 0) = - 221.8 A
![]()
|